Transformer Differential Protection Relay : ADR233B - V2
Back
General Description :

All the relay are designed using latest numerical technology and having programmable digital input and outputs to minimized external contact multiplication electromechanical relays. All relays are tested for EMI / EMC noise as per international IEC specifications. The basic electronics hardware is common for all relays. The user interface for all relays are similar only protection logic is different, this make very easy to use. General features of all relays are as given below:




Features :
Large 20x4 LCD display
Password Protection for all setting
Disturbance Recorder. 50 cycles of actual waveform of voltage & current (45 pre-fault & 5 post fault) are captured & saved in the built-in memory with date time stamping, for analyzing fault condition & fault location.
 
IEC 601870-5-103 or IEC61850 Protocol
Separate Communication Prot for SCADA (RS485) as well as Local testing (RS232C)
 
Very low burden on CT and PT
Online display of V,I,Active/Reactive Power, Primary secondary parameter, Logical / Physical status etc.
Continuous monitoring of module's internal hardware and alarm generation in case of failure of any critical components.
 
Facility to synchronized Relay time with SCADA network
 
10 Digital Output contacts for local alarm Tele-signalling & Control
 
9 Optically isolated digital status input for monitoring of status and avoid used of external relay logic
 
100 nos of event memory, event such CB close, Trip, status change, relay pkp etc. All events are with date and time stamped up to 1ms
 
 
Standard Specifications :
Programmable Dual Bias Characteristics
Wide Bias Setting 10% to 50%
Programmable Pick-up characteristic
Selectable 2nd harmonies restrain 10% to 80%
for Detection of transformer charging condition
 
5th harmonics restrain for CT saturation condition
Instantaneous Protection
Software base Vector group selection
Non Restrain Time delay backup protection
Breaker Failure Protection (LBB)

REF Protection

The relay is designed using modular removable terminal, having CT sorting arrangement. This make very easy for removing relay for maintenance and calibration and testing. Most of the relays are multifunction and having large numbers of setting.
Model Functional Details Cabinet Style
    ADR233B Transformer Differential Protection Relay CSE-H-150    

Download leaflet
User Manual Please send Enquiry
 
Curve
C1= For IDMT 10N-3secs. Normal Inverse 1
C2 = For IDMT 10N-1.3secs. Normal Inverse 2
C3 = For IDMT 10N-1.5secs. Very Inverse
C4 = For IDMT 10N-0.8secs. Extremely Inverse
C5 = For IDMT 10N-13.3secs. Long Time Inverse
C6 = For Definite Time.


Ashida Electronics - Provides high quality and effective Transformer Protection in India and Capacitor Protection.For more information on the basics of Capacitor Protection and transformer protection from www.ashidaelectronics.com
 
Veiw more Products
ADR111A ASHIDA Numerical Single Pole OC/EF Protection Relay
ADR133A ASHIDA NUMERICAL 3 POLE DIFFERENTIAL RELAY
ADR233A ASHIDA NUMERICAL 3 POLE DIFFERENTIAL RELAY
ACAG14 Instantaneous / Definite Time Over Current & Earth Fault Current Relay
 
Company Profile | ISO Certificates | Awards/Aprovals | Products | Projects | Careers | Contact us